If you have difficulty in submitting comments on draft standards you can use a commenting template and email it to admin.start@bsigroup.com. The commenting template can be found here.
Replace sixth paragraph by the following two paragraphs:
This document applies to accessories with screwless-type terminals with a rated current up to and including 125 A for series I and 100 A for series II.
This document applies to accessories with insulation piercing terminals, with a rated current up to and including 32 A for series I and 30 A for series II.
Replace the first paragraph by:
Compliance is checked by manual test and, for accessories having rated operating voltage exceeding 50 V with enclosures of resilient or thermoplastic material, by means of the gauge shown in Figure 215.
Delete two paragraph and the note after Table 3
Delete Table 216
Replace first, second, third and fourth paragraph of page 37 and Table 216 by:
Compliance is checked by inspection and by the by the test of 20, 21 and 22
Replace second, third and fourth paragraph by:
Compliance is checked by test of 8.2.3.
STANDARD SHEET 2-II (continuation 1)
Replace table of page 50 by the following table:
Dimensions in millimetres
Ratedcurrent e1 a) l2 l3 t v A 0–2 min. min. min. 2P + E 31 75 38 or 41 0–1,0 4 8 16/20 3P + E 35 80 44 or 47 0–1,0 5 8 3P + N + E 39 90 50 or 53 0–1,0 7 8 2P + E 41 90 51 or 54 0–1,0 7 8 32/30 3P + E 41 90 51 or 54 0–1,0 7 8 3P + N + E 46 105 57 or 60 0–1,5 8 9
STANDARD SHEET 2-VIIIa
Replace note b) by:
b) The dimension t is 10 mm minimum for a minor key of metal and 18 mm minimum for a minor key of insulating material