If you have difficulty in submitting comments on draft standards you can use a commenting template and email it to admin.start@bsigroup.com. The commenting template can be found here.
This part of IEC 60331 specifies the test apparatus and procedure and gives the performance requirements, including heat rate and temperature curve for power cables of rated voltage from 250 V up to and including 18/30 kV which are required to maintain circuit integrity when subject to Hydro Carbon Fire / Pool fire.
Requirements are stated for an identification that may optionally be marked on the cable to signify compliance with this document.
CAUTION The test given in this document may involve the use of dangerous voltages and temperatures. Suitable precautions should be taken against the risk of shock, burning, fire and explosion that may be involved, and against any noxious fumes that may be produced.
Decision 40. of 20/1896/DL.
The fire test defined in annex A of IEC 61892-4 needs to transfer to the IEC 60331 series as a standard giving TC 20 WG 18 control of this, specifically working with fire tests of cables.
You are now following this standard. Weekly digest emails will be sent to update you on the following activities:
You can manage your follow preferences from your Account. Please check your mailbox junk folder if you don't receive the weekly email.
You have successfully unsubscribed from weekly updates for this standard.
Comment on proposal
Required form fields are indicated by an asterisk (*) character.