Find out what cookies we use and how to disable themThis British Standard specifies requirements and test methods for the
construction and performance of cables that:
• have a thermosetting insulation of rated voltage 300/500 V;
• emit limited amounts of smoke (see 15.5) and corrosive gases when
subjected to relevant tests;
• are primarily intended for use in walls, partitions and building voids;
• have a screen that can carry the fault current required for a selected size
and type of protective device, that operates within a given time if the cable
is penetrated by a nail or similar fixing (see 16.4).
To achieve a satisfactory safety performance of the cable when installed, both
the selection of protective device and the maximum current rating is critical.
The proposed amendment would:
1. Modify Clause 5, Conductors to remove reference to BS EN 13603. And, replace with New Annex
2. Modify table 3, Schedule of tests, to include a similar entry to that in BS 7629-1:2015+A1:2019
3. Modify Clause 6.5 changing the test from BS EN 50267-2-1 to BS EN IEC 60754-3
4. Modify Clause 8.2 changing the test from BS EN 50267-2-1 to BS EN IEC 60754-3
5. Modify Clause 10.5 changing the test from BS EN 50267-2-1 to BS EN IEC 60754-3
6. Modify table 3 for clauses a mentioned in 3, 4, 5 above to reference BS EN IEC 60754-3
7. Add new clause 16.6 for corrosive and acid gas, with wording that the non-metallic materials shall be tested in accordance with BS EN IEC 60754-3 and that the results shall not exceed the levels in BS EN IEC 60754-3, Table A.2