Find out what cookies we use and how to disable themThis British Standard specifies tests and requirements for power cables with XLPE insulation and metal sheath and their accessories for rated voltages from 66 kV (Um = 72.5 kV) to 132 kV (Um = 145 kV) for fixed installations.
NOTE 1 Cable systems to this standard do not normally have high electrical stresses at the conductor or insulation screen.
If the calculated nominal electrical stresses at the conductor screen will be higher than 8.0 kV/mm and/or at the insulation screen higher than 4.0 kV/mm, then attention is drawn to the need to conduct a prequalification test in accordance with IEC 60840:2011, Clause 13.
This British Standard is applicable to single-core cables and three-core cables with separate cores and to their accessories for usual conditions of installation and operation. It is not applicable to special cables and their accessories, such as those designed for submarine cables, for which modification to the standard tests might be necessary or special test conditions might need to be devised.
NOTE 2 Annex A gives tests and requirements for cable bonding leads. Annex B gives tests and requirements for sheath voltage limiters (SVLs), while Annex C gives tests and requirements for link housings. Annex D gives an additional water blocking test for phase conductors.
The proposed amendment would add an additional annex Specifying tests for gas-immersed terminations in the case of using an alternative insulating gas to the usual SF6 gas type.
You are now following this standard. Weekly digest emails will be sent to update you on the following activities:
You can manage your follow preferences from your Account. Please check your mailbox junk folder if you don't receive the weekly email.
You have successfully unsubscribed from weekly updates for this standard.
Comment on proposal
Required form fields are indicated by an asterisk (*) character.