We use cookies to give you the best experience and to help improve our website
Find out what cookies we use and how to disable themThis document defines the calculation method for determining the fan energy index (FEI), which is an energy efficiency metric for fan duty points. This metric provides a standardized and consistent basis to compare fan energy performance across fan types and sizes at a given fan duty point.
This document is applicable to fans driven by motors and fans without drives. It is not applicable to circulating fans or air curtains.
The fan energy index can only be calculated for fan duty points above a minimum air power of 125 W (where air power is the product of volume flow rate and fan static pressure) or above a minimum volume flow rate of 2.0 m3/s.
This document differs from others in this series in that the fan is not evaluated at its peak efficiency value. Rather, the fan is evaluated at every duty point within its stated performance range. In doing so, this document addresses both the design and the proper selection of fans for reduced power consumption.
The fan energy index provides a consistent basis to compare fan energy performance across fan types and sizes at a given fan duty point. This document can be used by fan specifiers to communicate fan efficiency design intent and by those selecting fans to compare the energy use of various fan options. With improvements in technology and manufa
You are now following this standard. Weekly digest emails will be sent to update you on the following activities:
You can manage your follow preferences from your Account. Please check your mailbox junk folder if you don't receive the weekly email.
You have successfully unsubscribed from weekly updates for this standard.
Comment on proposal
Required form fields are indicated by an asterisk (*) character.