BS EN IEC 60947-7-5 BS EN 60947-7-5 Low-voltage switchgear and controlgear -. Part 7-5: Ancillary equipment - Terminal blocks for aluminium conductors

Source:
IEC
Committee:
PEL/121/1 - Low voltage switchgear and controlgear
Categories:
Switchgear and controlgear. Low voltage
Comment period start date:
Comment period end date:
Number of comments:
0

Comment by:

Scope

This part of IEC 60947 specifies requirements for terminal blocks with screw-type or screwless-type clamping units primarily intended for industrial or similar use and to be fixed to a support to provide electrical and mechanical connection. This document can be used for terminal blocks for connection between aluminium conductors, copper-clad aluminium conductors, aluminium to copper conductors, aluminium to copper-clad aluminium conductors, or copper to copper-clad aluminium conductors. It applies to terminal blocks intended to connect round conductors, with or without special preparation, having a cross-section between 2,5 mm2 and 300 mm2 (AWG 12 to 600 kcmil), intended to be used in circuits of a rated voltage not exceeding 1 000 V AC (up to 1 000 Hz) or 1 500 V DC.

In this document, copper-clad and nickel-clad aluminium conductors are considered as aluminium conductors.

This document can be used as a guide to qualify terminal blocks for conductors out of aluminium not complying with IEC 60228 (e.g. smaller than 10 mm2, flexible or other materials). This document can also be used as a guide to qualify other types of terminal blocks for conductors out of aluminium other than feed through terminal blocks (e.g. partially insulated terminal blocks).

NOTE 1 AWG is the abbreviation of "American Wire Gage" (Gage (US) = Gauge (UK)).

kcmil = 1 000 cmil;

1 cmil = 1 circular mil = surface of a circle having a diameter of 1 mil;

1 mil = 1/1 000 inch.

This document does not apply to clamping units:

–        dedicated to any other types of switchgear and controlgear;

–        for connection by crimping, brazing, soldering or welding;

–        for data and signalling circuits;

–        for flat quick-connect terminations, insulation-piercing connecting devices and twist-on connecting devices, for which separate parts are under consideration.

NOTE 2 In some countries, national regulation for installation rules can allow different cross-sections. For internal wiring (inside enclosures), other rules or product standards can be applicable.

NOTE 3 For connections to copper conductors only, IEC 60947–7–1:2009 is applicable.

NOTE 4 In USA, UL 1059[5] applies and in Canada, CSA C22.2 No. 158[6] applies.

Where applicable in this document, the term "clamping unit" is used instead of the term "terminal". This is taken into account in case of reference to IEC 60947–1:2020.

Read draft and comment

Comment on proposal

Required form fields are indicated by an asterisk (*) character.


Please email further comments to: debbie.stead@bsigroup.com

Follow standard

You are now following this standard. Weekly digest emails will be sent to update you on the following activities:

You can manage your follow preferences from your Account. Please check your mailbox junk folder if you don't receive the weekly email.

Unfollow standard

You have successfully unsubscribed from weekly updates for this standard.

Error