BS 7350 Heating and chilled water systems − Double regulating globe valves and flow measurement devices – Specification

Source:
BSI
Committee:
PSE/18/2 - Gate, globe, diaphragm and check valves
Categories:
Water supply | Water heating
Comment period start date:
Comment period end date:
Number of comments:
1

Comment by:

Scope

This document specifies requirements for metallic double regulating globe valves and flow measurement devices having flanged, wafer, threaded or compression end connections.

This document specifies requirements for performance and function including materials, pressure/temperature ratings, dimensions, testing, hydraulic performance and marking.

This document applies to metallic double regulating globe valves and flow measurement devices in the form of fixed and variable orifice valves and as individual orifice fittings used for low temperature hot water and medium temperature hot water heating and chilled water systems.

The range of nominal sizes covered is:

a)    flanged:

       DN10, DN15, DN20, DN25, DN32, DN40, DN50, DN65, DN80, DN100, DN125, DN150, DN200, DN250, DN300;

b)    threaded:

       ⅜, ½, ¾, 1, 1¼, 1½, 2;

c)     compression:

        15 mm, 22 mm 28 mm.

The range of pressure designations is covered by:

a)    Flanged:

       PN10, PN16, PN20, PN25, PN40 

b)    Threaded:

        PN10, PN16, PN20, PN25, PN32, PN40

c)     Compression:

         PN16.

NOTE 1 For compression ends and loose nut/union end bodies in copper alloy materials there are no PN designations. Use BS EN 1254-2, which gives the details of the body ends for compression end valves covered in this document rather than the PN designation system given in BS EN 1333.

NOTE 2 Low temperature hot water heating systems have a maximum temperature of 90 °C and Medium Temperature Hot Water systems have a maximum temperature of 120 °C as per CIBSE Guide B1 2016 [5].

Information to be supplied by the purchaser is given for information in Annex A. The correspondence between DN, NPS and nominal diameters is given for information in Annex B.

Read draft and comment

Comment on proposal

Required form fields are indicated by an asterisk (*) character.


Please email further comments to: debbie.stead@bsigroup.com

Follow standard

You are now following this standard. Weekly digest emails will be sent to update you on the following activities:

You can manage your follow preferences from your Account. Please check your mailbox junk folder if you don't receive the weekly email.

Unfollow standard

You have successfully unsubscribed from weekly updates for this standard.

Error